6–82 339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
S3 PROTECTION CHAPTER 6: SETPOINTS
Figure 6-34: Negative Sequence Overvoltage logic diagram
SETTING
NEG SEQ OV FUNCTN
Disabled = 0
Latched Alarm
Alarm
Trip
SETTING
BLOCK 1:
Off = 0
BLOCK 2:
Off = 0
BLOCK 3:
Off = 0
NEG SEQ OV
ALARM PKP
S
R
LATCH
896831.cdr
LOGIC OPERAND
NEG SEQ OV
ALARM OP
LOGIC OPERAND
OR
OR
AND
AND
AND
AND
OR
AND
AND
INPUTS
Emergency Restart Input
Lockout Reset Input
SETTINGS
Off = 0
Lockout Reset
Off = 0
Emergency Restart
S4 CONTROLS
NEG SEQ OV
State: Operate
Alarm
TARGET MESSAGE
ANY ALARM OP
NEG SEQ OV
TRIP OP
ANY TRIP OP
S
R
LATCH
NEG SEQ OV
Trip
State: Operate
TARGET MESSAGE
ANY ALARM PKP
NEG SEQ OV
TRIP PKP
ANY TRIP PKP
AND
AND
OR
S3 NEGATIVE SEQ OV
S3 NEGATIVE SEQ OV
OR
Reset Input
Reset
Off = 0
AND
OR
KEYPAD RESET
ANY LATCHED ALARM OP
NEG SEQ OV
State: Pickup
Alarm
TARGET MESSAGE
NEG SEQ OV
State: Pickup
Trip
S3 NEGATIVE SEQ OV
Vab
NEG SEQ OV PKP:
Vbc
Vca
RUN
Van
Vbn
Vcn
V > PICKUP
2
DeltaWye
896835A1.cdr
SETTING
Phase Voltage Inputs
(associated setpoints)
SETTING
NEG SEQ OV DELAY
t
PKP
S3 NEGATIVE SEQ OV
SETTING
OUTPUT RELAY X
Do Not Operate, Operate