CHAPTER 6: SETPOINTS S3 PROTECTION
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 6–87
Figure 6-37: Underfrequency logic diagram
SETTING
UNDRFREQ FUNC
Disabled = 0
Latched Alarm
Alarm
Trip
SETTING
BLOCK 1:
Off = 0
BLOCK 2:
Off = 0
BLOCK 3:
Off = 0
UNDRFREQ ALARM PKP
S
R
LATCH
LOGIC OPERAND
UNDRFREQ ALARM OP
LOGIC OPERAND
OR
OR
AND
AND
AND
AND
OR
AND
AND
INPUTS
Emergency Restart Input
Lockout Reset Input
SETTINGS
Off = 0
Lockout Reset
Off = 0
Emergency Restart
S4 CONTROLS
UNDRFREQ
State: Operate
Alarm
TARGET MESSAGE
ANY ALARM OP
UNDRFREQ TRIP OP
ANY TRIP OP
S
R
LATCH
UNDRFREQ Trip
State: Operate
TARGET MESSAGE
ANY ALARM PKP
UNDRFREQ TRIP PKP
ANY TRIP PKP
AND
AND
OR
S3 UNDERFREQUENCY
S3 UNDERFREQUENCY
OR
Reset Input
Reset
Off = 0
AND
OR
KEYPAD RESET
ANY LATCHED ALARM OP
UNDRFREQ
State: Pickup
Alarm
TARGET MESSAGE
UNDRFREQ
State: Pickup
Trip
S3 UNDERFREQUENCY
Vab
UNDRFREQ PICKUP:
RUN
Van
f < PICKUP
DeltaWye
896833A1.cdr
SETTING
Phase Voltage Inputs
(associated setpoints)
SETTING
UNDRFREQ DELAY
t
PKP
S3 UNDERFREQUENCY
Frequency Measurement
Wye-connected VT: Van
Delta-connected VT: Vab
SETTING
MIN VOLTAGE
Van > Minimum
S3 UNDERFREQUENCY
f = 0
OUTPUT RELAY X
SETTING
Do Not Operate, Operate