CHAPTER 6: SETPOINTS S4 CONTROLS
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 6–129
Local Mode is set if the input for the LOCAL MODE setpoint is asserted. In this mode, the
REMOTE OPEN and REMOTE CLOSE setpoints are deactivated, regardless of the status of
their selected inputs. Breaker Open and Breaker Close commands from the KEYPAD BKR
OPEN and KEYPAD BKR CLOSE setpoints will be active, if the breaker operation is set to
Local Mode (i.e. the selected input under the LOCAL MODE setpoint asserted).