4–78 850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
SYSTEM CHAPTER 4: SETPOINTS
Figure 4-18: Disconnect Switch State Detection logic diagram
SETPOINT
89a CONTACT
FlexLogic operand =1, Off = 0
SETPOINT
89b CONTACT
FlexLogic operand =1, Off = 0
FlexLogic operand
(SW1 89a state)
FlexLogic operand
(SW1 89b state)
AND AND
XOR
PKP
S
R
LED: ALARM
LATCH
OR
AND
OR
OR
ANDAND
FLEXLOGIC OPERANDS
SW1 CLOSED
FLEXLOGIC OPERANDS
SW1 OPENED
FLEXLOGIC OPERANDS
SW1 DISCREPANCY
OR
FLEXLOGIC OPERANDS
SW1 NOT CONFIGURED
SETPOINT
ALARM DELAY
t
Positive
Edge
SETPOINT
RESET ALARM
FlexLogic operand, Off = 0
FLEXLOGIC OPERANDS
SW1 INTERMITTENT
FLEXLOGIC OPERAND
89a CONTACT
FLEXLOGIC OPERAND
89b CONTACT
894193A1.cdr