CHAPTER 4: SETPOINTS PROTECTION
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4–123
TARGETS
Range: Self-reset, Latched, Disabled
Default: Self-reset
Figure 4-45: Phase Time Overcurrent Protection logic diagram
894149A1.CDR
SETPOINTS
Phase A current (Ia)
SETPOINT
FUNCTION:
Disabled
Trip
PICKUP:
CURVE:
TDM:
Phase B current (Ib)
Phase C current (Ic)
OR
Operate Output Relay 1 (TRIP)
LED: PICKUP
OR
Alarm
OR
OR
Phase Currents
AND
Latched Alarm
AND
RUN Ia > PICKUP
RUN Ib > PICKUP
RUN Ic > PICKUP
Adjust PKP
Adjust PKP
Adjust PKP
SETPOINTS
BLOCK :
Off = 0
LED: ALARM
RESET
Command
AND
S
R
LATCH
Configurable
FlexLogic Operands
Phase TOC 1 OP
Phase TOC 1 OP:C
Phase TOC 1 OP:B
Phase TOC 1 OP:A
FlexLogic Operands
Phase TOC 1 PKP
Phase TOC 1 PKP C
Phase TOC 1 PKP B
Phase TOC 1 PKP A
SETPOINTS
INPUT:
Phasor,
RMS
RESET:
From Cold Load Pickup
TOC Pickup Raise
From Autoreclose
TOC Pickup Raise
SETPOINTS
OUTPUT RELAYS
Do Not Operate, Operate
LED: TRIP
Set
Dominant
From Manual Close Blocking
TOC Pickup Raise
RUN
Calculate
Voltage
Restraint
Multiplier
SETPOINT
VOTAGE RESTRAINT:
Disabled
Enabled
AND
Ph A Reverse (from Phase
Directional OC element)
SETPOINTS
DIRECTION:
Disabled
Forward
Reverse
OR
AND AND
AND AND
Ph B Reverse (from Phase
Directional OC element)
Same Logic as for Phase A
Ph C Reverse (from Phase
Directional OC element)
Same Logic as for Phase A
AND
OR
SETPOINTS
SIGNAL
INPUT:
CT Bank 1 –
J1
CONFIGURABLE IN
845
USED ONLY IN
850
USED ONLY IN 845