4–226 850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
PROTECTION CHAPTER 4: SETPOINTS
PICKUP DELAY
Range: 0.000 to 600.000 s in steps of 0.001 s
Default: 0.100 s
This setting specifies a time delay for the function.
DROPOUT DELAY
Range: 0.000 to 600.000 s in steps of 0.001 s
Default: 0.000 s
This setting specifies a dropout time delay for the function.
OUTPUT RELAY X
For details see Common Setpoints
.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
The element will be blocked, when the selected operand is asserted.
EVENTS
Range: Enabled, Disabled
Default: Enabled
The element will be blocked, when the selected operand is asserted.
TARGETS
Range: Self-reset, Latched, Disabled
Default: Self-reset