4–388 850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
CONTROL CHAPTER 4: SETPOINTS
MAXIMUM RATE PER HOUR
Range: 1 to 50 per hour in steps of 1
Default: 25
The setpoint specifies the number of Reclosures per hour that can be attempted before
Reclosure goes to Lockout.
OUTPUT RELAY X
For details see Common Setpoints
.
EVENTS
Range: Disabled, Enabled
Default: Disabled