CHAPTER 4: SETPOINTS CONTROL
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4–389
Figure 4-165: Autorecloser - AR1 Rate Supervision logic diagram - “PAGE 3”
894073A2.cdr
AR1 SHOT RATE PER
HOUR:
SET TO ZERO
INCREMENT COUNTER
DECREMENTS SHOTS
FROM 60 MIN. AGO
SETPOINTS
CLEAR AR1 RATE
DATA
YES
NO
SETPOINTS
AR1 MAX RATE PER
HOUR:
RUN
Counter >= Max Rate
SETPOINTS
AR1 RATE SUPERV
FUNCTION:
Disabled = 0
Alarm
FLEXLOGIC OPERAND
AR1 Rate High
AR1 Rate High - Lockout
To Page 1
AR1 RATE SUP
OUTPUT RELAYS (3-7):
SETPOINTS
Do Not Operate,
Operate
From Page 2
AR1 close
PAGE 3 (AR1 RATE SUPERVISION)
Lockout
OR
AND
FLEXLOGIC OPERAND
AR1 Rate HI Lockt
ALARM (Default)
STATUS