GEK-113032A W650 Wind Generator Protection System 7-41
7 IEC 61850 PROTOCOL 7.2 IEC 61850 PROFILE FOR W650
7
7.2.4.5 COMMON DATA CLASS SPECIFICATIONS FOR ANALOGUE SETTINGS
a) ANALOGUE SETTING (ASG).
ING CLASS (INTEGER STATUS SETTING)
GEING_6
ATTRIBUTE
NAME
ATTRIBUTE TYPE FC TRGOP VALUE/VALUE RANGE M/O/C
DATAATTRIBUTE
Setting
setVal ENUMERATED SP OpModEnum
(any, two, all phases )
M
d Vstring255 DC O
GEING_7
Attribute
Name
Attribute Type FC TrgOp Value/Value Range M/O/C
DATAATTRIBUTE
Setting
setVal ENUMERATED SP InModEnum
(phase-phase, phase-ground )
M
d Vstring255 DC O
ASG CLASS (ANALOGUE SETTING)
GEINTASG
ATTRIBUTE
NAME
ATTRIBUTE TYPE FC TRGO
P
VALUE/VALUE RANGE M/O/C
DATAATTRIBUTE
setting
setMag
i
AnalogValue SP AC_NSG_M
INT32
configuration, descripcion and extension
units
SIUnit
multiplier
Unit CF O
ENUMERATED(Byte) M
ENUMERATED(Byte) O
minVal INT32 CF O
maxVal INT32 CF O
stepSize INT32 CF O
d Vstring255 DC O
GEFLOATASG
Attribute
Name
Attribute Type FC TrgOp Value/Value Range M/O/C
DATAATTRIBUTE
setting
setMag
f
AnalogValue SP AC_NSG_M
FLOAT32
configuration, descripcion and extension
units
SIUnit
multiplier
Unit CF O
ENUMERATED(Byte) 5 M
ENUMERATED(Byte) 0 O
minVal FLOAT32 CF 5.e-002 O
maxVal FLOAT32 CF 160 O
stepSize FLOAT32 CF 1.e-002 O