B-24 W650 Wind Generator Protection System GEK-113032A
B.6 EVENTS STATUS REQUEST (ALARMS) APPENDIX B
B
B.6.4 ACKNOWLEDGEMENT OF EVENTS (ALARMS)
For acknowledging the alarms we must simply write message to the 0xf324 address with 12 data registers. Each bit means
an event, if we want to acknowledge an alarm, its corresponding bit must be set to ‘1’ (in order within the 192 bits).
NOTE: it must be borne in mind the independence of the acknowledgement condition, for its reading and its change,
depending on the communication channel
There are 6 channels:
LOCAL: by MMI or COM-2 (front and rear accessible).
REMOTE: by COM-1
NET 1: nowadays by any net communication
NET 2: (it does not exist in version 1.4x and lower)
NET 3: (it does not exist in version 1.4x and lower)
NET 4: (it does not exist in version 1.4x and lower)