E-4 W650 Wind Generator Protection System GEK-113032A
E.1 FACTORY DEFAULT SETTINGS APPENDIX E
E
PRODUCT SETUP>COMMUNICATION SETTINGS >IEC 870-5-104
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Enable or disable the protocol
operation
Function DISABLED N/A [DISABLED – ENABLED]
Listening TCP port in the relay TCP Port 2404 N/A [0 : 65535]
Address in the ASDU header
Common Addr of
ASDU
255 N/A [0 : 65535]
Number of seconds for instantaneous
meterings
Cyclic Meter Period 0 1 s [0 : 3600]
Not implemented Synchronization Event 0 N/A [0 : 3600]
IEC 870-5-104 NOTES
Note 1: Cyclic Meter Period 0 value means no spontaneous meterings
PRODUCT SETUP>COMMUNICATION SETTINGS > SNTP
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Port used UDP port 123 1 [1 : 65535]
IP Address OCT 1 Server IP Oct 1 0 1 [1 : 255]
IP Address OCT 2 Server IP Oct 2 0 1 [1 : 255]
IP Address OCT 3 Server IP Oct 3 0 1 [1 : 255]
IP Address OCT 4 Server IP Oct 4 0 1 [1 : 255]
PRODUCT SETUP>COMMUNICATION SETTINGS >CAN OPEN
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
CAN Open Node Id CAN Open Node Id 1 N/A [1 : 127]
CAN Open Baud CAN Open Baud 125 Kbs N/A [125 : 500]