(Repeat to attach a second sensor to the S5000 transmitter).
5. Connect the sensor to the “Sensor 1” position on the electronics assembly. a) If using a second sensor, connect it to the second sensor position.
NOTICE If only using one sensor and it is connected to “Sensor 2” position, the S5000 will enter Sensor Missing fault. See Disable
Sensor in 4.2.2 Sensor Setup for details on how to clear this fault.
Figure 13 Connecting Sensor to the Figure 14 SOURCE/SINK Switch Location
Stack and Grounding Terminal
6. Verify the sensor connector is firmly seated on the terminal board.
7. Attach the sensor’s ground to either of the grounding screws inside the S5000 housing.
8. Set the analog output to SOURCE or SINK using tweezers, flat head screwdriver or similar tool.
a) With the display board removed, locate “S1” switch on the main board (see Figure 14 ).
b) Set “S1” switch in the required position:
For SINK, set switch to the right side.
For SOURCE, set switch to the left side.
9. Replace the display module. Push firmly on the board stack
NOTICE Ensure that the electronics assembly is fully engaged in the mounting holes. If not fully seated, the touch interface
performance can be negatively affected.
10. Replace the cover by turning clockwise.
11. Tighten the set screw located on the lid using a 1.5 mm Allen wrench.
NOTE: The JB5000 junction box is not compatible with IR400 and passive sensors
3.4.5 Integrated Mounting Points
The S5000 transmitter can be surface mounted without any additional brackets using the integrated mounting tabs.
Figure 15 Integral Mounting Tabs
Mounting Points JB5000 Junction Box
The JB5000 junction box can be mounted directly using the 4 integrated 10-32 threaded holes on the back of the enclosure
or with the use of a mounting bracket (P/N 10206570).
3.4.6 Adjustable Pipe Mount
A Universal Pipe Mount Kit (P/N 10176946) can be used to mount the S5000 on pipes ranging from 20-150 mm in diameter. Two brackets are mounted over the
top of the integrated mounting tabs and fitted with an adjustable pipe band (not included).