Figure 20 Sunshield with Universal Pipe Mount
3.4.9 Mounting with an SM5000 Sampling Module
An aspirated (P/N 10158101) and a DC pump (P/N 10043264) model are available for use with the S5000 with the Digital Sensor. For more information on
mounting requirements and use with the SM5000 sampling modules, see the SM5000 operating manual(s).
Figure 21 Mounting the SM5000 with a Digital Sensor
SM5000 is not for sale in EU.
Diffusion Supervision must be disabled when using the SM5000.
3.5 Installing a Remote Sensor Junction Box
Sensors mounted remotely must use the S5000 junction box. The junction box housing is the same construction as the transmitter. The mounting options and
instructions for connecting the sensor are the same for sensors connected directly to the S5000 transmitter housing. The junction box is available in 316 Stainless
Steel. Sensors can be remote mounted up to 100 m from the transmitter housing, as long as the S5000 transmitter is mounted within maximum distance from the
power supply, as indicated in Table 1 . The junction box does not have an illuminated display and has two connectors for attaching a single sensor input and an
output connects to the transmitter. A 16 AWG 4 element cable with a braided shield should be used for the electrical
connection between the junction box and the S5000 transmitter. Specific cable recommendations are available upon request.