5120 Quick Start Procedure
5120-SI-SO
• Turnon gas supply to TEG. Hold down the button on Shut O󰀨 (SO) valve. The spark igni-
tionsystem(SI)shouldbeginclickingandthesoundofcombustionheardwithin15seconds.
Continueholdingthebuttonfor90secondsthenreleaseit.TheSOvalveshouldremainopen
andtheTEGshouldcontinuetooperate.
• Adjustthefuelpressureto10-15%lessthannotedonDataNameplate.
• Installthejumperclipbetweenterminals3&4ofTB-1
• Afteronehourmeasurethe voltage,V
set
,betweenterminals2(+)and 4(-)ofTB-1.TheV
set
shouldbeapproximately6.7volts.SeeSection2.6toadjustingforambienttemperature.
• Returnthejumpercliptobetweenterminals1and2ofTB-1
• ApplyCustomerload
Fuel Pressure
• Propanestartup: 41-45kPa 6-6.5psi
• NaturalGasstartup: 24-31kPa 3.5-4.5psi