GlobalPowerTechnologies 3-13
5120
Symptom Probable Cause RemedyandProcedure
Lowoutputpowerorlow
voltage.
Incorrectset-upvoltagefor
sitetemperature.
DeterminerequiredV
set
forpresentconditions.Section2.6.1.
Insucientcoolingaround
ns.
Clearnsofanydebris.
Dirtyfuellter
Drainregulatorsedimentbowl.
Section3.2.2.1.
Changelter.Section3.2.2.2.
Oriceplugged. Changeorice.Section3.2.2.3.
SOvalvemalfunctioning. CheckSOvalve.Section3.2.6
Incorrectairsupply.
Adjustairsupply.Section2.6.4.
Cleanairscreen.Section3.2.3
Incorrectfueladjustment. Adjustfuelregulator.Section2.6.5
LimiterConverterneeds
adjustingorrepair.
Checkswitchsettings.
CheckoutputvoltageadjustmentPot.
Powerunitfaulty. Checkmomentaryopencircuitvoltage,
section3.2.1
Outputpowerorvoltage
istoohigh.
Incorrectfueladjustment. Lowerfuelpressure.Section2.6.5
IncorrectLimiterConverter
adjustment.
Re-adjusttheoutputvoltageadjust-
mentPot.