Programmable Temperature & Humidity Controller
52
1. Control mode
- Select control mode
2. SSR Period
- Set the control output period when SSR mode is selected
3. Output Direction
- Set output direction
4. Anti Reset Wind-up
- Select operation mode automatic/manual
- When the mode is 'MANUAL', operator can set the ARW zone manually.
▶ Temperature/Humidity Control output
2. Control/transmission output setting
Parameter Setting Range Default
Output mode SSR, SCR
SSR
SSR Period 1 ~ 1000 1
Output Direction Direct, Reverse Reverse
ARW AUTO, MANUAL AUTO
ARW Zone 50 % ~ 200 % 100 %
[Control Output Parameter]
●
Temperature
Fig. 67) Temperature Control output Fig. 68) Humidity Control output