6.6
V10 Flicker
98
Quick Start Manual
5.
Making 3196 settings (recording settings)
Event detection is not possible using the V10 flicker value.
Accordingly, event settings are not made.
RECORDING
Make the following settings.
Shows the maximum interval that you can record
with the settings above.
Items Settings
Rec. Data
Power, AVE
(You can observe the MAX and MIN
values on the voltage fluctuation graph
when AVE is set.)
Memory Full
STOP
Interval
30 sec (6 days 22 hours 10 minutes)
Select item
Select from
pull-down
menu
Confirm
6.
Starting the recording
Use the same method as when measuring power fluctuation. (page 66)
The V10 reference value is generated automatically using
AGC (automatic gain control) generated over 1-minute with a low
pass filter.
BPF (bandpass filters) are used for flicker detection. Due to the
effect of the HPF (highpass filter), the first and second
V10
flicker values measured may be large if measurement is begun
immediately after making settings. Therefore, after making con-
nections and settings, we recommend waiting about 3 minutes
before starting measurement.