Measurement Method
6.4 Monitoring Interruptions
83
6.
Making 3196 settings (event settings)
VOLTAGE
Make the following settings.
Dips and voltage interruptions are observed as
RMS values.
When you want to detect partial dropouts in a
waveform:
Items Settings
Urms DIP
(Voltage Dip)
90%
(Voltage is 90% of nominal 230 V: 207 V)
U Interrupt
(Voltage interrup-
tions)
10%
(Voltage is 10% of nominal 230 V: 23 V)
Items Settings
U wave
(Voltage waveform
comparison)
(ON) Set the event level.
You can detect partial waveform drop-
outs on the order of ms.
U Transient
(Voltage Transient)
(ON) Set the event level.
You can detect partial waveform drop-
outs on the order of µs.