4.5.2 Wire sizes for ES Series
Field minimum wire sizes for the power source
Model Power Source Max. Current (A)
Power Source Cable Size Transmitting Cable Size
EN60 335-1 (2*) EN60 335-1 (2*)
All Indoor Units (1*)
230V/1φ/50Hz
5 0.75 mm
2
0.75 mm
2
RAS-2HVRN1E 13 1.5 mm
2
RAS-2.5HVRN1 16 2.5 mm
2
RAS-3HVRNS 18 2.5 mm
2
RAS-4HVRNS1E 18/24 4.0 mm
2
RAS-5HVRNS1E 26
6.0 mm
2
RAS-6HVRNS1E 26
RAS-8HRNSE
400V/3φ/50Hz
20
6.0 mm
2
0.75 mm
2
RAS-10HRNSE 23
N O T E
(1*): Except RPI-8.0-10.0
Follow local codes and regulations when selecting field wires.
The above wire sizes marked with (2*) are selected at the maximum current of the unit according to the european
standard, EN60 335-1. Use wires not lighter than the ordinary neoprene (polychloroprene) sheathed flexible
cord (code designation H05RN-F).
In the case that the power cables are connected in series, add each unit maximum current and select the wire
sizes in next table.
The ground cable size must comply local code: IEC 245, No. 571.
4 Electrical Wiring
97
SMGB0060 rev. 1- 12/2010