7.5 Check list
7.5.1 Check list for IVX Series
Check list on test run
MODEL:  
SERIAL No.  
COMPRESSOR MFG No.  
NAME AND ADDRESS OF
CUSTOMER:
 
DATE:  
1 Is the rotating direction of the indoor coil fan correct? __________
2 Is the rotating direction of the outdoor coil fan correct? __________
3 Is there any abnormal compressor sound? __________
4 Has the unit been operating for at least twenty (20) minutes? __________
5 Check the room temperature:
Inlet
No 1
DB____ °C
WB ____ °C
No 2
DB____ °C
WB ____ °C
No 3
DB____ °C
WB ____ °C
No 4
DB____ °C
WB ____ °C
Outlet
DB____ °C
WB ____ °C
DB____ °C
WB ____ °C
DB____ °C
WB ____ °C
DB____ °C
WB ____ °C
Inlet
No 5
DB____ °C
WB ____ °C
No 6
DB____ °C
WB ____ °C
No 7
DB____ °C
WB ____ °C
No 8
DB____ °C
WB ____ °C
Outlet
DB____ °C
WB ____ °C
DB____ °C
WB ____ °C
DB____ °C
WB ____ °C
DB____ °C
WB ____ °C
6 Check the outdoor temperature:
Inlet
DB____ °C
WB ____ °C
Outlet
DB____ °C
WB ____ °C
7 Check the refrigerant temperature: Operating mode (cool or heat).
Discharge gas temperature
Td = _____ °C
Liquid pipe temperature Te = _____ °C
8 Check the pressure:
Discharge pressure
Pd = _____kg/cm
2
G
Suction pressure Ps = _____kg/cm
2
G
9 Check the voltage:
Rated voltage
_____V — —
Operating voltage L1–L2______V L1–L3______V L2–L3______V
Starting voltage _____V — —
Phase imbalance 1-(V/Vm) = — —
10 Check the compressor input running current
Input
_____kW
Running current _____A
11 Is the refrigerant charge adequate? __________
12 Do the operation control devices operate correctly? __________
13 Do the safety devices operate correctly? __________
14 Has the unit been checked for refrigerant leakage? __________
15 Is the unit clean inside and outside? __________
16 Are all the cabinet panels fixed? __________
17 Are all the cabinet panels free from rattles? __________
18 Is the filter clean? __________
19 Is the heat exchanger clean? __________
7 Test Run
181
SMGB0060 rev. 1- 12/2010