¿ Troubleshooting by alarm code
Alarm code
01
Activation of the safety device in the indoor unit
The RUN LED flickers and "ALARM" is displayed on the remote control switch.
The unit number, the alarm code and the unit code are alternately displayed on the set temperature section.
The unit number and the alarm code are displayed on the display of the outdoor unit PCB.
This alarm code is displayed when the contact between #1 and #2 of CN14 is not closed over 120 seconds during
the cooling process, the heating process or the fan operation.
Phenomenon
Cause Check item
Action
(Turn OFF the main
switch)
Activation of the float switch
High Drain Level Clogging of the drainage Check the drain pan
Remove the clogged foreign
particles
Faulty float switch
Fault
Check the continuity when
the drain level is low
Replace the float switch if
faulty
Faulty contacting
Measure the resistance by
means of the tester
Fix the looseness and
Replace the connector
Faulty connection Check the connections Repair the connection
Faulty indoor unit PCB
Check PCB by means of the
self-check mode *1)
Replace PCB if faulty
N O T E
*1): Refer to section 7.3.1, see on page 299 and Self-Checking procedure of the Indoor Unit PCB (only for
RPK), see on page 303.
Alarm code "01" is not displayed at the RPK series.
8 Troubleshooting
207
SMGB0060 rev. 1- 12/2010