N O T E
• L & H are the length & height indicated in the above chart.
• For twin, the length is the distance between the outdoor unit and the farthest indoor unit.
• Piping length after branch pipe (B,C & D):
1 After branch pipe B,C & D, the pipe length should be shorter than 10 m.
2 All branch pipe, B, C & D (it depend of case), should be balanced.
Twin
Triple
B & C difference B,C & D difference
≤
 8 m
≤
 6 m
3.3.3 Refrigerant piping selection
Select the piping connection sizes according to the following procedures
• Between outdoor unit and branch pipe: Select the same pipe connection size as the pipe size of the outdoor unit.
• Between branch pipe and indoor unit: Select the same pipe connection size as the pipe size of the indoor unit.
Piping connection size of outdoor unit, indoor unit and distributor
Outdoor Unit
Pipe Size Multikit & Distributor
Liquid Piping Gas Piping Twin Triple Quad
RAS-3HVRNME Ø9.53 Ø15.88 TE-03N / E-102SN2 — —
RAS-4H(V)RNM1E Ø9.53 Ø15.88 TE-56N / E-102SN2 TRE-06N —
RAS-5H(V)RNM1E Ø9.53 Ø15.88 TE-56N / E-102SN2 TRE-06N
TRE-56N+(TE-03N or
TE-56N) 
(3)
RAS-6H(V)RNM1E Ø9.53 Ø15.88 TE-56N TRE-06N
TRE-56N+(TE-03N or
TE-56N) 
(3)
RAS-8HRNM Ø9.53
(1)
Ø25.40
(2)
TE-08N / E-162SN2 TRE-810N QE-810N
RAS-10HRNM Ø12.70 Ø25.40
(2)
TE-10N / E-162SN2 TRE-810N QE-810N
RAS-12HRNM Ø12.70 Ø25.40
(2)
TE-10N / E-162SN2 TRE-810N QE-810N
  N O T E
The sizes of the indoor and outdoor units are different. Adjust the flare adapter (accessories) to the joint part of
the indoor piping.
• (1) Select the size of piping ø12.7 when the length is over 70 m (only for RAS-8HRNM).
• (2) If using ø28.60, the actual length is reduced to 75 m.
• If using ø22.20, the actual length is reduced to 100 m., but with a significant reduction in capacity.
The following Multikits can also be used for RAS-(8-12)HRNM.
Outdoor Unit
Multikits
RAS-8HRNM E-162SN-102SN
RAS-10HRNM E-162SN-102SN
RAS-12HRNM E-162SN-102SN