Blocked in Inlet Side
The length A is as show in the following table:
L A
0<L=1/2H 500 or greater
1/2H<LH
1000 or greater
When L > H, use a base for outdoor unit to make L H.
Close the base not to allow the outlet air bypassed.
Outlet Side Blocked
Upper Side Open
Single Installation Multiple Installation (Two units or more)
Pipe Cover
Ensure 250 mm or more of the side space on the pipe cover side.
Allow 250 mm of service space between units. Both right and left sides
shall be open.
Pipe Cover
Pipe Cover
Be sure to use the fan direction guide. Leave open both right and left sides.
Be sure to use the fan direction guide. Allow 250 mm of service space
between units. Serial installation allowed up to two units.
Leave open both right and left sides.
The length A is as show in the following table:
L A
0<L=1/2H 100 or greater
1/2H<LH
200 or greater
When L > H, use a base for outdoor unit to make L H.
Close the base not to allow the outlet air bypassed.
The length A is as show in the following table:
L A
0<L=1/2H 150 or greater
1/2H<LH
250 or greater
When L > H, use a base for outdoor unit to make L H.
Close the base not to allow the outlet air bypassed.
2 Unit Installation
13
SMGB0060 rev. 1- 12/2010