2.5 Installation space (Initial ckeck)
2.5.1 RAS-(2-3)HVRN(1)(E)(S)
Blocked in Inlet Side
Upper Side Open
Single Installation Multiple Installation (Two units or more)
Ensure 250 mm or more of the side space on the pipe cover side. Allow 250 mm of space between units. Leave open both right and left sides.
Be sure to use the fan direction guide. Leave open both right and left sides.
Ensure 250 mm or more of the side space on the pipe cover side.
Be sure to use the fan direction guide.
Allow 250 mm of service space between units. Leave open both right and
left  sides. When  subject  to direct  sunlight  on the  back  wall,  ensure the
length marked with . be 400 or greater.
Ensure 250 mm or more of the side space on the pipe cover side.
Upper Side Blocked
Single Installation Multiple Installation (Two units or more)
Fifteen mm of space is acceptable for one of the lateral sides.
Ensure 250 mm or more of the side space on the pipe cover side.
Allow 250 mm of service space between units. Leave open both right and
left sides.
Ensure 250 mm or more of the side space on the pipe cover side.
Be sure to use the fan direction guide. Leave open both right and left sides.
Ensure 250 mm or more of the side space on the pipe cover side.
Be sure to use the fan direction guide.
Allow 250 mm of service space between units. Leave open both right and
left sides. Serial installation allowed up to two units.
Ensure 250 mm or more of the side space on the pipe cover side.
2 Unit Installation
12
SMGB0060 rev. 1- 12/2010