Output connections
Indication Connections
o1
CN7
o2
CN7
Specification of the components for a correct installation
Component
Manufacturer or specifications Remarks
Auxiliary relay (X3)
OMRON mini power relay model: MY1F or
equivalent
Voltage between relay terminals 12 Vdc - 75
mA
(SS1) (x1), (x2) contact example Manual type
Voltage between terminals of the 230V - 5
mA contactor
3P connector cable
Optional part PCC-1A (capable of connecting
the JST XHP -3 connector)
Five wires with connectors as one set
Wire (control) Voltage: 12V DC. 0.5 mm
2
Wire (power) Voltage 230V 2.0 mm
2
N O T E
The connection of the input signal is only an example.
Keep the CN1 and CN2 wires as short as possible.
Do not run the wires along 230 V/400 V ac power cables separately install them at a distance of more than 30 cm.
(The cables may intersect).
If you install the wires along a power supply wire, insert the wires in a metal conduit tube and ground one end
of the tube.
The maximum wiring length is 70 m. If you use this function, it is recommended that you use safety devices
such as an electrical leakage breaker or a smoke detector.
6.1.2 Configuration
Available optional signals
The units have the following signals that are described in the following table.
6 Optional functions