2.5.2 RAS-(3-6)H(V)RNM(1)E / RAS-(4-10)HVRNS(1)E
Blocked in Inlet Side
Upper Side Open
Single Installation Multiple Installation (Two units or more)
100 mm or more of the side space is acceptable on the service cover side.
Dimensions  in  (  )  shows  numbers  especially  for  IVX  4-10  HP  and  ES
8/10 HP. 150 or more (200 or more) of the back space is acceptable when
the right and left sides are open.
Allow 100 mm of space between units. Leave open both right and left sides.
Dimensions  in  (  )  shows  numbers  especially  for  IVX  4-10  HP  and  ES
8/10 HP.
Be sure to use the fan direction guide. Leave open both right and left sides.
Be sure to use the fan direction guide. Allow  100 mm of space between
units. Leave open both right and left sides.
When subject to direct sunlight on the back wall, ensure the length marked
with . be 500 or greater.
Upper Side Blocked
Single Installation Multiple Installation (Two units or more)
100 mm or more of the side space is acceptable on the service cover side.
Dimensions  in  (  )  shows  numbers  especially  for  IVX  4-10  HP  and  ES
8/10 HP.
Allow 100 mm of space between units. Leave open both right and left sides.
Dimensions  in  (  )  shows  numbers  especially  for  IVX  4-10  HP  and  ES
8/10 HP.
Be sure to use the fan direction guide.
Leave open both right and left sides.
Be sure to use the fan direction guide. Allow  100 mm of space between
units. Leave open both right and left sides.
Serial installation allowed up to two units.
 
2 Unit Installation
16