b Using an H-LINK II system for air conditioning systems with a central control panel (CSNET WEB or PSC-64S).
In case of using a central control panel, you must connect the H-Link II wiring to all the systems. The easiest way
of connection to the H-LINK II system is usually to connect the available outdoor units.
In this case, the CS-NET WEB wiring can be connected at any point of the H-LINK II wiring.
In case of not using a central control device when the electrical wiring is performed. In this case, you must connect
the H-LINK II wiring to all the systems.
Usually, to connect the outdoor units is the easiest implementation to connect them in the system.
N O T E
• Do not make wiring in a loop. in order to avoid malfunctions of the system.
4 Electrical Wiring
105
SMGB0060 rev. 1- 12/2010
4