Pressing
RUN/STOP
switch
Stop of inverter
Stop of MC
I.U.: Indoor unit
O.U.: Outdoor unit
MD: OFF
Power to EHW:OFF
Power to CMC: OFF
Power to MIF: OFF
Temp.
on the top of
comp.
After 1
min. 20 sec.
(for unit with drain pump)
> 60 ºC
55 ºC
Power to CH : ON
Power to CH : OFF
Power to Y52C: OFFStop of MOF
(for unit with EHW)
Power to YH2: OFF
Yes
No
RUN/STOP lamp: OFF
DRY, set fan speed & set temp. indication: continuously ON
STOP
Power to
I.U.: OFF
Power to
O.U.: OFF
Indication LCD: OFF
Power to PCB in I.U.: OFF
Power to CH: OFF
Power to PCB in O.U.: OFF
from 1
Pressing
AUTO-LOUVER switch
Stop of
AUTO-LOUVER
Start of
AUTO-LOUVER
Alternatively
only for air panel
or indoor unit with
auto-louver
5 Control System
129
SMGB0060 rev. 1- 12/2010
5