In the TEST RUN mode, the red RUN LED of the receiver is turned ON and the green TIMER LED flickers (0.5 seconds
ON ↔ 0.5 seconds OFF) (*2). Then, the timer switches off for two hours.
N O T E
If the yellow LED does not turn ON, the commands from the remote control switch may not have reached the
receiver. Send the commands again.
(*2) In the case of the RPK model, the TIMER LED is turned OFF.
5 : Adjust the angle of the air grille as follows. The air louver has a mechanism for the auto-swing function. Do not move
the louver by hand forcefully.
Select the FAN mode by pressing the MODE switch.
Set the louver angle by pressing the LOUVER switch.
6 : Stop the test run (normal)
The test run stops automatically after two hours.
You stop the test run by pressing the RUN/STOP switch again.
After the test run has finished, check that the red RUN LED and the green TIMER LED turn OFF.
7 : Stop the test run (abnormal) for the PC-RLH 9/11.
If you cannot use the PC-LH3A because of battery shortage or any other reason, perform the emergency operation as
follows.
COOL switch: Press the COOL switch in order to start the cooling process.
Press the COOL switch again in order to stop the cooling process.
HEAT switch: Press the HEAT switch in order to start the heating process.
Press the HEAT switch again in order to stop the heating process.
N O T E
During the emergency operation, the yellow LED blinks (0.5 seconds ON / 0.5 seconds OFF).
Alarm code display
If some malfunction occurs because of the activation of a safety device or any other reason, the red RUN LED blinks
(0.5 seconds ON / 0.5 seconds OFF).
Refer to the chapter 8 for the alarm code table.
The alarm code displays the number of blinks of the green DEF LED and the yellow FILTER LED as shown bellow:
Green DEF LED: Digit 2 of the alarm code blinks.
Yellow FILTER LED: Digit 1 of the alarm code blinks. (Alphabet code: A=10 blinks, B=11 blinks, C=12 blinks, etc.).
The red RUN LED (1 second ON / 1 second OFF) means that there is an abnormal transmission between the indoor
units and the outdoor unit.
Yellow FILTER LED
Green DEF LED
DEF LED blinks three times
(0.5 seconds ON / 0.5 seconds OFF)
FILTER LED blinks 5 times.
(0.5 seconds ON / 0.5 seconds OFF)
Alarm code:
7 Test Run
179
SMGB0060 rev. 1- 12/2010