Alarm code
97
Abnormal operation of thermistor for the KPI (outdoor temperature thermistor) for IVX Series
The RUN LED flickers and “ALARM” is displayed on the remote control switch.
The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit
number and the alarm code are displayed on the display of the outdoor unit PCB.
This alarm code is displayed when the thermistor is short-circuited or cut during the KPI operation. The system is
automatically restarted when the fault is removed
Is THM2 connected to (intake)
of PCB?
Connect it
No
Yes
Is the resistance of THM2
between 0.24kΩ and 840kΩ?
Faulty thermistor
No
Yes
Faulty PCB
Phenomenon Cause Check item
Action
(Turn OFF the main switch)
Faulty air inlet thermistor
Fault Check the resistance Replace the thermistor if faulty
Incorrect connection Check the connection
Repair the wiring and the
connections
Faulty PCB
Replace PCB and check the
operation
Replace PCB if faulty
N O T E
This data is applicable to the following thermistors:
Indoor unit discharge air temperature
Indoor unit liquid refrigerant temperature
Indoor unit air inlet temperature
Outdoor temperature
Outdoor unit evaporating temperature
Indoor unit gas piping