N O T E
• All units are in mm.
• Do not stack more than two units in the height.
• If L is larger than H, mount the units on a base so that H is equal or greater than L.
– H: Unit height (1650 mm) + base concret height
L A B
0 < L
≤
1/2 H
600 or more 300 or more
1/2H < L
≤
H
— —
• In this situation, ensure that the base is closed and does not allow the airflow to short circuit.
• In each case, install the outdoor unit so that the discharge flow is not short-circuited.
• When the installation dimension results the one marked with an (*), mount the air flow guide.
2 Unit Installation
21
SMGB0060 rev. 1- 12/2010