The activating conditions of protection control are shown in the table below
Code Protection Control Activating Condition Remarks
P0
Low-Pressure Ratio Control at Cooling
Operation
Compression Ratio ε < 2.2
=> Frequency Increase
ε = (Pd+0.1)/(Ps+0.1)
P1
High-Pressure Ratio Control at Heating
Operation
Compression Ratio ε > 7.5
=> Frequency Decrease
ε = (Pd+0.1)/(Ps+0.1)
P2
High-Pressure Increase Protection High Pressure Switch for Control is activated
=> Frequency Decrease
P3
Over Current Protection Inverter Output Current > (*1)A
=> Frequency Decrease
P4
DIP-IPM, ISPM or IPM Temperature
Increase Protection
Inverter Fin Temperature
RAS-8~10HRNSE > 100 ºC
RAS-3~6HVRNS(E) > 80 ºC
=> Frequency Decrease
P5
Discharge Gas Temperature Increase
Protection
Temperature at the top of compressor is high
=> Frequency Decrease
Temperature at the top of compressor > 107 ºC
=> Indicate P5
P6
Frost Formation Protection
TL 2 °C Over 3 minutes => Frequency Decrease
TL: Liquid Piping,
Temperature of Indoor Unit
P9
Unbalance Power Source Detecting Inverter Output Current > (*3)A
=> Frequency Decrease
P
Current Demand Control Inverter Output Current > (*2)A
=> Frequency Decrease
In case of
Demand Control Setting
Pb
Low-Pressure Decrease Protection Low Pressure Switch for Control is activated.
=> Frequency Decrease
PC
Cold Draft Protection
TO 10 ºC and ε 2.6 => Frequency Decrease
ε = (Pd+0.1)/(Ps+0.1)
TO: Outlet Temperature of
Indoor Unit
P7
Inverter Retry Automatic Stoppage of Transistor Module,
Activation of Electronic Thermal or Abnormal Current
Sensor
When activating 3 times in 30
minutes, “48”, “51”, “53” or “54”
alarm is indicated.
P8
Inverter Retry Insufficient/Excessive Voltage at Inverter
Circuit or PCB Connector Part
When activating 3 times in 30
minutes, “06” or “55” alarm is
indicated.
N O T E
During protection control (except during alarm stoppage), the protection control code is indicated.
The protection control code is indicated during protection control and turns off when cancelling the protection
control.
After retry control, the condition of monitoring is continued for 30 minutes.
The Maximum value of IVX series (*1) and (*2) are as follows:
The Maximum value of ES series (*3), (*4) and (*5) are as follows:
(1*)
HP
380-415V 220-240V
4 5 6 8 10 12 3 4 5 6
Current (A) 8.0 12.0 12.0 17.5 20.0 21.0 16.0 16.0 24.0 24.0
(2*)
HP
380-415V 220-240V
Demand setting
4 5 6 8 10 12 3 4 5 6
Current (A)
100% 4.0 5.5 20.0 8.5 10.0 12.0 11.5 13.0 17.0 20.0
75% 3.0 4.0 15.0 6.0 8.0 12.0 8.5 10.0 13.0 15.0
50% 2.0 2.0 10.0 4.0 5.0 7.5 5.5 6.5 8.5 10.0
8 Troubleshooting
297
SMGB0060 rev. 1- 12/2010