EasyManua.ls Logo

Hitachi RAS-3HVRNS - Page 323

Hitachi RAS-3HVRNS
482 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5. Touch [+] of the tester to [P] of DIP-IPM (soldered part), and
[-] to DIP-IPM U, V, W terminals to measure the resistance.
Normal if all three terminals have 1 kΩ or greater.
6. Contrary to [5], touch [-] of the tester to [P] of DIP-IPM
(soldered part), and [+] to DIP-IPM U, V, W terminals to
measure the resistance
. Normal if all three terminals have 30 kΩ or greater.
(Resistance gradually increases during measurement.)
7. Touch [-] of the tester to [N] of ISPM (soldered part), and [+]
to ISPM U, V, W terminals to measure the resistance.
Normal if all three terminals have 1 kΩ or greater.
8. Contrary to [7], touch [+] of the tester to [N] of DIP-IPM
(soldered part), and [-] to DIP-IPM U, V, W terminals to measure
the resistance.
Normal if all three terminals have 30 kΩ or greater.
(Resistance gradually increases during measurement.)
1. Tester.
2. Contact with specified terminals to measure.
Non-faulty if [9] – [13] are checked and satisfied.
(Measure with 1 kΩ range of a tester.)
Internal Circuit of ACT Part of Inverter Module
1. External Appearance and Internal Circuit of Transistor
Module .
N O T E
DO NOT use a digital tester
9. Check items [1] – [8].
10. Touch [+] of the tester to DIP-IPM DCL2 terminal, and [-] to
[P] of ISPM/DIP-IPM (soldered part) to measure the resistance.
Normal if all three terminals have 100 kΩ or greater
11. Contrary to [10], touch [-] of the tester to DIP-IPM DCL2
terminal, and [+] to [P] of DIP-IPM (soldered part) to measure
the resistance.
Normal if all three terminals have 1 kΩ or greater.
12. Touch [+] of the tester to DIP-IPM DCL2 terminal, and [-] to
[N] of DIP-IPM (soldered part) to measure the resistance.
Normal if all three terminals have 100 kΩ or greater.
13. Contrary to [12], touch [-] of the tester to DIP-IPM DCL2
terminal, and [+] to [N] of DIP-IPM (soldered part) to measure
the resistance.
Normal if all three terminals have 10 kΩ or greater.
(Resistance gradually increases during measurement.)
1. Tester.
2. Contact with specified terminals to measure.
1
2
1
1
2
8 Troubleshooting
315
SMGB0060 rev. 1- 12/2010
8

Table of Contents

Related product manuals