1
4-6x10 Long Hole
2
5 (Both Sides) - M5 Screw (attachement)
Material Galvanized sheet metal + baked painting
Color UTOPIA Beige
Weight 4.0 kg
Accessories
Fixing screw x 4 [M5 (SUS) x 30]- Unit
Fixing Screw x 10 [M5 (SUS) x 12]- Wind Ward
Installation manual
Installation
restriction
“Guard net”, “Air flow guide” or “Snow protection hood” is
not available to install with Wind guard
Attaching example of air wind guard
• Attach the air flow guide to the air discharge grille with four (4) screws (supplied).
• The fixing holes are located at 4 positions on the grille. (Screw tightening torque 2.4 ~ 3.1 N.m)
• Do not remove the air discharge grille for air flow guide installation.
C A U T I O N
• If the air guide is installed without discharge grille, it may cause injury due to rotating fan.
Two windguard covers installation
1 Air discharge grille
2 Outdoor unit
3 M5 fixing screw x4 (Accessories)
Service space
• Both sides of the outdoor unit should be open.
• No obstacles should be placed in the air discharge side.
1 Min.150 mm
2 Outdoor unit
3 Wind guard