7. Vibration-Proof rubber 1.
N O T E
Fix the lead wire for the compressor firmly not to contact with metal sheet edge and high temperature piping.
Fixation of the compressor to the bottom plate
Compressor position 1 2 3 4
Vibration-proof rubber 1 x x x x
Vibration-proof rubber 2 x x
Nut x x
¿ Removing High pressure switch and pressure switch for control
1 Remove the service cover according to the section Removing service cover, see on page 414 .
2 Collect the refrigerant from the check joint according to the section Removing the compressor, see on page 419 .
3 a Pull out the Faston terminals.
b Remove the high pressure switch (PSH) and pressure switch for control (PSC) from the brazing part of the discharge
pipe.
1. Upper cover.
2. Rear cover.
3. Electrical box.
4. Brazing part.
5. Pressure switch for control (PSC).
6. Discharge pipe.
7. High pressure switch (PSH).
N O T E
The capacitors (CB1 and CB2) are located on the pressure switch.
Pay attention not to touch the capacitors when removing work is performed. If not, electrical shock may occur.
1
2
3
4
4
5
6
7
10 Servicing
422
SMGB0060 rev. 1- 12/2010