3 Air flow guide
4 Passage side
¿ Wind guard
Specifications
Model WSP-335A
Quantity 2 per unit
1
1
2
2
2
2
3
1 Mounting dimension
2 Air flow
Material
Galvanized sheet metal +
baked painting
Color Gray (1.0Y8.5/0.5)
Weight 5.5 kg
Accessories
Fixing screw
x 4 [M5 (SUS) x 12]
Installation manual
Installation
restriction
“Guard net”, “Air flow guide” or “Snow protection
hood” is not available to install with Wind guard
Attaching example of air wind guard
Attach the air flow guide to the air discharge grille with four (4) screws (supplied).
The fixing holes are located at 4 positions on the grille. (Screw tightening torque 2.4 ~ 3.1 N.m)
Do not remove the air discharge grille for air flow guide installation.
C A U T I O N
If the air guide is installed without discharge grille, it may cause injury due to rotating fan.
Two windguard covers installation
1 Air discharge grille
2 Wind guard
3 Outdoor unit
4 M5 fixing screw x4 (Accessories)
1
1
2
2
3
4
2 Unit Installation