¿ Air flow guide
Specifications
Model
AG-335A
Quantity 2 per unit
1
1
2
1 Mounting dimension
2 Air flow guide
Air discharge
direction
Upward (downward), left & right
Material Weather proof polypropylene resin
Color Gray
Weight 1.9 kg
Accessories
Fixing screw x 4 [M5 (SUS) x 20]
Installation manual
Installation
restriction
“Wind Guard” or “Snow protection hood” is not
available to install with air flow guide. (“Guard net” is
available to be installed together.)
Attaching example of air flow guide
Attach the air flow guide to the air discharge grille with four (4) screws (supplied).
The fixing holes are located at 4 positions on the grille. (Screw tightening torque 2.4 ~ 3.1 N.m)
Do not remove the air discharge grille for air flow guide installation.
C A U T I O N
If the air guide is installed without discharge grille, it may cause injury due to rotating fan.
Two flow guides installation
1 Air discharge grille
2 Air flow
3 Air flow guide (see the note)
4 Outdoor Unit
5 M5 fixing screw x4 (Accessories)
N O T E
Air flow direction of both air flow guides should be the
same.
Service space (In case of upward air discharge)
In case of right and left sides air discharge, enough space for
air discharge is required.
The downward air discharge is also available. In such case,
install the base under the unit to secure enough space for air
discharge.
In case of serial units installation, air discharge should be
upward.
1 Min. 200 mm