Process Displays
Device Control
98 900 Control Station User Guide Revision 9
May 2014
Device Control
The Device Control function block is normally used to control pumps. Based on certain events the device
will be placed into the appropriate state.
Table 30 Device control display details
Item Description
State READY, PRESTART, STARTING, RUNNING, STOPPING, DISABLED, or
FAILED. READY (off state) is the initial state of the block. See Table 31
Device states.
Seconds Current Timer value. READ ONLYCounts down to zero.
The Start Delay Timer is active in the Prestart state
The Stop Delay Timer is active in the Stopping state
The Feedback timer is active in the Starting state while the Feedback
input pin is OFF.
The Feedback timer is active in the Running state (if the Feedback
input turned on in the starting state.)
Run Request Green when device is requested to be put in the Starting or Running state.
Active Green when state is Running or Stopping.
Failed Red when the control is in the Failed state (the controlled device reported
a failure or did not start up in time; device is being monitored for a manual
or automatic reset).
Reset Select to reset the control when it is in the FAILED state to return it to the
READY state.