Diagnostics I/O Module Diagnostics and I/O Calibration
44 900 Control Station User Guide Revision 9
May 2014
I/O Module Error Status
Table 22 I/O Module Error Status
Status Possible Cause Controller Action What to do
HI CJ TEMP
Possible causes of
this diagnostic are:
1. One of the two CJs
on the module is
indicating a
temperature reading
greater than 70
degrees C.
2. Both cold-junction
sensors are failing to
convert.
3. The CJs are
converting properly,
but their differential is
greater than 10
degrees C.
1. Associated AI blocks that are configured
as T/Cs set their fail pin on, their warn pin
off, and their output pin to the failsafe value.
2. Associated AI blocks that are configured
as T/Cs set their IO status to CJ High
Temperature for reason 1 or CJ Failure
for possible causes 2 and 3.
3. Associated rack monitor blocks module
fail pin is turned on.
4. Associated rack monitor blocks RACK
OK pin is turned off.
5. Associated rack monitor blocks
HITEMP pin is turned on.
6. SYSTEM MONITOR block’s HITEMP
pin is turned on.
7. SYSTEM MONITOR block’s HW OK
pin is turned off.
1. Improve ventilation to rack
2. Replace AI module
MISMATCH
The installed module
does not agree with
the module required
for the control
strategy downloaded
in the configuration
file.
1. Associated blocks set their fail pin on,
their warn pin off, and their output pin to the
failsafe value.
2. Associated blocks set their IO status to
Channel No Comm.
3. Associated rack monitor blocks module
fail pin is turned on.
4. Associated rack monitor blocks RACK
OK pin is turned off.
5. SYSTEM MONITOR block’s HW OK
pin is turned off.
1. Verify configuration
2. Replace module with the correct one.