Setpoint Programmers
Setpoint programmer Operate
126 900 Control Station User Guide Revision 9
May 2014
Item Description
Title Name of the selected setpoint programmer block.
SP Profile Information
Profile Number Memory location of the profile that is being run by the Setpoint
Programmer.
Profile Name Name of the selected profile.
Profile Description Description of the selected profile.
Total Elapsed Time Total time the profile has been in Run, Hold and GHold states.
State READY: Profile is at the beginning of segment and is ready to run. All
events are OFF.
HOLD: Profile is paused at the setpoint value shown.
RUN: Profile is executing normally.
GHOLD: Profile is paused because of excessive deviation.
STOP: Profile has reached the end of the last segment.
DISABLE: Profile is prevented from starting until the programmer disable
control is ON.
Segment Information
Segment number Current segment
Elapsed Time Time elapsed in the segment. Run time only.
Time Remaining Time remaining in the segment.
Segment Type
Text shows type of current segment: ramp or soak.
The current and next segment types are shown graphically. In the above
example, the current segment is ramping up, the next segment is a soak.
Operation Buttons
Run Start a program that is in HOLD or READY state.
Hold Put program in HOLD.
Advance Jump to the next segment.
When the program is already in the last segment, the advance request is
ignored.
Programs cannot be advanced to the first segment. Current state must
either READY or HOLD.