Setpoint Programmers
View/Edit profile
130 900 Control Station User Guide Revision 9
May 2014
Item Description
Guaranteed Hold Type Guaranteed Hold, if enabled here, will hold the profile value if a PV to the
profile (typically a control loop’s PV) deviates specified amounts above or
below the profile output.
None: No segments have guaranteed hold enabled.
Per Seg: Lets you select specific segments for guaranteed hold where
you set up the profile ramps and soaks.
All Soaks: All soak segments will have a guaranteed hold enabled.
All Segs: All segments will have guaranteed hold enabled.
Loop Start Segment The first segment of the loop.
Loop End Segment The last segment of the loop.
Loop Cycles Number of times the loop segments will execute. Zero (0) means the
segments will be repeated forever.
Jog Segment Segment to which the program will jump to when the JOG discrete input is
pulsed.
Restart Rate This recovery ramp rate is provided in the event of a power loss while a
program is running. The Restart Rate value is used to return the process
to the last operating setpoint prior to power loss.
Auxiliary Output Label A second analog value is available for each segment of the program. It is
a fixed soak value and can be used to provide a setpoint value for a
secondary control loop in the process.
Auxiliary Engineering Units This is the engineering unit text associated with the AUX OUT.
Fast Forward Fast Forward is a way to check for proper functioning of the profile’s
events and outputs, without having to wait for the profile to execute at its
normal speed. When FAST FORWARD is ON, the program will run at a
speed 60 times faster. When FAST FORWARD is OFF, the program will
run at normal speed.