Digital Room Thermostat (DTS92)
To bind a OpenTherm Bridge (R8810) to a Digital Room
Thermostat (DTS92) to control an OpenTherm™ boiler...
On the OpenTherm Bridge
1
Press and hold the button for 15 seconds
(until the red LED blinks rapidly) to
clear any previous binding data
2
Press and hold the button again for 5
seconds (until the red LED blinks slowly)
On the Digital Room Thermostat
3
Press and hold the power button for 2
seconds to put the unit into standby
4
Press the up and down arrows together
for 3 seconds – it should display 'INst'
5
Press the down arrow – it should display 'COnt'
6
Press the up arrow three times
– it should display 'CLr'
7
Press the power button once to
clear any previous binding data
8
Press the up arrow – it should display 'COnt'
9
Press the power button once
to send the binding signal to the
Wireless OpenTherm Bridge
The LED on the Wireless OpenTherm
Bridge should stop blinking and turn
OFF. If not go back and re-bind.
Digital Room
Thermostat (DTS92)
Wireless OpenTherm
Bridge (R8810)