Fire Alarm Control Panel Compact
FB 798238.GB0 / 10.14 29
2ABC
3 3
range from
zone : +0001+
zone 1
CLR 5
JKL
3 3
range to
zone : +0001+
zone 1
CLR
3DEF
8
TUV
ESC
3
event 2
1 type : none
3
1
3
DEF
2ABC
3
type 1/4
1 none
2 panel state
3 activation zone(s)
4 activation detector(s)
5 fault zone(s)
6 fault detector(s)
7 deactivation zone(s)
3
event 2
1 type : activation zone(s)
2 range from : 005
3 range to : 008
3
3
trigger events
1 event 1 : pre-alarm panel
2 event 2 : activation zone(s)
3 event 3 : none
4 event 4 : none
5 event 5 : none
6 event 6 : none
7 event 7 : none
3
1 function type : common
2 hardware
3 inverted : off
4 trigger events : 2
5 pulse duration (s) : off
6 pulse latched : off
7 trigger prevention : 0
control zone >0003<
3
3
*event 2
1 type : activation zone(s)
2 range from :
3 range to :
3
Fig. 41: >Programming outputs< menu screens
Event 2
Type
Activation zone(s)
Range from / to
Control zone 1 was
programmed with
the second
assignment to
“pre-alarm panel”
and activation zones
5-8.
save to RAM