Time synchronization
The following topics are important for understanding and planning the time synchronization
requirements of your Experion LX system.
Experion time requirements
Reliable and coordinated time is an important element in an Experion system. It is used in
many aspects of the system including:
n
control functions
n
redundancy options
n
intersystem communications of supervisory systems
Supported time protocols
When deploying a topology, the time protocols supported should be considered.
Device
CDA
client
SNTP
client
NTP
client
PTP
client
1
CDA
server
SNTP
server
NTP
server
PTP server
C300 X X X
PGM X X X
Wireless Device
Manager
X X
2
PMD X X
RTU
3
X
Moxa switch (IEC
61850 compliant)
X X X X
4
XExperion time
requirements above
1
PTP IEEE-1588 version 1 and PTP IEEE-1588 version 2 are supported for Safety Manager devices.
For all other devices, only PTP IEEE-1588 version 2 is supported.
2
Limited to servicing Field Device Network(FDN) only
3
Also supports DNP3 for time synchronization
4
Limited to IEC 61850 networks only
Time synchronization
Honeywell 2017 36

Table of Contents

Other manuals for Honeywell Experion LX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Experion LX and is the answer not in the manual?

Honeywell Experion LX Specifications

General IconGeneral
BrandHoneywell
ModelExperion LX
CategoryControl Systems
LanguageEnglish

Related product manuals