MPA2C3 Installation Guide 9
Up to a current of 6A, a cable cross-section of at least 0.75 mm² must be used,
up to 10A a cable cross-section of at least 1.00 mm².
Do not lengthen or connect the activating line in the housing without double
insulation.
Do not store loose, unused connecting cables in the housing.
Route the incoming cable separately through the provided recess to the
terminal.
Minimum distances must be observed: Clearance: 4 mm, creepage distance: 5
mm.
Strip the ends of the cores (approx. 4 mm).
Use core end sleeves to clamp leads.
Fix the incoming cable with the provided cable binder to the housing.
Observe the VDE safety regulations and provisions of the local electricity
supplier.
Caution: Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries
according to caution on the battery and all local and national regulations.
Caution: Replace the DC battery if it shows any sign of corrosion or leakage or if the battery is 2
years old or older. Replacing battery must be done by skilled person.
Safety Symbol
The following symblos are used in this manual:
Read carefully more details, regarding charging and discharging of battery.
Shock Risk-Isolate before attempting access.
Protective Earth
Caution- Instruction, or Information with vital importance for the safety of person-
nel, or equipment.