60 MPA2C3 Installation Guide
OSDP READER ADDRESS ASSIGNMENT FEATURE VIA PANEL
Usually OSDP readers are delivered with address “0”.
The reader needs to be readdressed to the appropriate address for the assigned
function per the above table. The readdressing can be done with the addressing
tool of the reader (see instruction or installation manual of the reader manufac-
turer).
The MPA2C3 panel has an auto addressing function.The procedure is described
below.
OSDP reader controls
When an invalid card has been swiped to the reader, the access is denied to the
card holder and the reader red LED will flash twice and generates two beeps.
This is different than the Wiegand controls.
Reader Connection
mode
RJ45 Connector
Reader Address Reader Function
OSDP READER
READER 1 1 Door1 IN reader
Wieg.A / OSDP 1 2 Door1 OUT reader
READER 3 3 Door3 IN reader
Wieg.A / OSDP 1 4 Door3 OUT reader