CHAPTER
9
ACS4C3 Installation Guide 171
TROUBLESHOOTING
Table 9-1 Troubleshooting Problems and Solutions
Problem Solution
The panel
powers up, but it
does not
respond to any
communicatio
n,
cards reads, or
input activation.
Ensure that the Address DIP switches are set the correct values. Turn
off the power (including battery), change the settings, and re-apply
the power.
No
communicatio
ns
exist with the
Ethernet port.
Only a panel set to be a Primary (Set Bit 3 of DIP switch 1 to ON) will
have communications on the Ethernet port. If you need to use that
port to access the panel, turn off the power (including the battery),
change the switch setting, and reapply the power.
Note: That if the panel is normally not a
Primary on a Multidrop
communication bus, then the Host RS-
485 connection J7/8 should also be
disconnected while Bit 3 of DIP switch
1 is ON. After completion of the
Ethernet session, turn off the power
(including the battery), change the
switch setting, reconnect the Host RS-
485 terminal block, and re-apply the
power.

Table of Contents

Other manuals for Honeywell MPA2C3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell MPA2C3 and is the answer not in the manual?

Honeywell MPA2C3 Specifications

General IconGeneral
BrandHoneywell
ModelMPA2C3
CategoryIP Access Controllers
LanguageEnglish

Related product manuals