EasyManua.ls Logo

Honeywell MPA2C3 - Ethernet Connection with Ethernet Virtual Loop - Multiple Locations

Honeywell MPA2C3
183 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MPA2C3 Installation Guide 141
Ethernet Connection with Ethernet Virtual Loop – Multiple
Locations
Figure 4-6 Ethernet Connection with Ethernet Virtual Loop – Multiple Locations
Note:
Network must provide DHCP server (or use dedicated Network configuration
with a router shown in next section).
Recommend that Network provide firewall protection from unauthorized access.
If the locations are in different Geographic time zones, it is recommended that
each time zone
should be served by its own “Ethernet Virtual Loop. The reason is that all
controllers on the same Ethernet Virtual loop must be set to the same
Geographic time zone.
The
network must allow the primary panel in Location 1 to connect to TCP port
#9876 in Locations 2 and 3.

Table of Contents

Other manuals for Honeywell MPA2C3

Related product manuals