Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15
47
Menu
Display
Description
Set Calibration
Execute zero/span calibration Set
calibration gas level
After zero, the option exists to proceed with span
calibration, or return to the Menu
Initialize Baseline
Note 3
Perform a baseline initialization (flammable-CAT
versions only)
Select Sensor
Note 3
Select the type of sensor from the sensor list. This
menu is only available for flammable / IR sensor
Select Gas
Note 3
Select the type of gas from the list. This menu is
only available for flammable / IR sensor.
Set Range
Set measuring range
Configure Inhibit
Note 1
Select inhibit current
Set timeout option (5 minutes increments)
Set Password
Enable/disable
password Set password
Default no password (Select ‘0000’)
Set Calibration
Interval
Set calibration interval, 30 to 365 days
User configurable option to display warning
Bump Test
Execute a ‘bump’ test to check gas response of the
sensor.
Force Current
Force analogue output to test functionality of GD control
system during system commissioning
Set Alarms
Note 2
Set alarm 1, alarm 2 levels, functionality and
operation (none/falling/rising)
Set Relays
Note 2
Set relay 1,2,3 type (alarm 1, alarm 2, fault and inhibit)
and action (energized/de-energized)