Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15
48
Note 1: To comply with IEC EN 60079-29-1 and EN 50104, if the Inhibit current is set to 4 mA, the
timeout option must be set. The maximum value for the timeout is 15 minutes.
Note 2: To comply with IEC EN 60079-29-1 and EN50104, the alarms must be configured as latching
by setting the corresponding relay to latching, even if the relay is not being used. If relays are used the
action must be configured as energized for fail safe operation.
Note 3: Init. Baseline, Select Sensor and Select Gas are available for flammable/IR sensors only.
Table 7 Transmitter menu descriptions
Relay Operation
Note 2
Configure relay on delay time, relay off delay time
and latch/non-latch
Set Location
Set location (or TAG number)
Set Temperature
Unit
Change temperature display unit.
°C (Celsius) or °F (Fahrenheit)
Check Alarm
functions
Simulate alarm situation to check the alarm system
without gas present at the sensor
Set deadband
Enable or disable the display deadband
Quit
Return to Monitoring mode